How To: Eliminate Superfluous "Critical" Alerts From APC Network Management Cards

Here’s another one to file under the, “web UI is inferior to the command line interface” category of gotchas.  First, the basics:

·         APC Symmetra UPS

·         AP9619 Network Management Card (latest firmware)

·         “Critical” alerts set to page On-Call Engineers

Ever since this UPS was installed, we had all “Critical” events being sent to the distribution list for paging the On-Call Engineers.

Here’s the problem… every time the UPS would pass a self-test, we’d receive a Critical Ticket, which would wake up the On-Call Engineers, who would then proceed to curse my name, close the ticket, and go back to bed after punching the pillow repeatedly.  Imagine getting this alert at 3 AM… how would that make you feel?

Each time this would happen, I would:

·         Check for upgraded firmware

·         Run through the wizards to #1) Clear the alerts and #2) Re-instate the alerts

·         Get cursed out again two weeks later when the scheduled self-test ran again

This got to be so frustrating that I just turned off self-tests altogether (not advised).

Finally, I called APC (thanks, D. Petrarc!) and they showed me the solution: The web UI doesn’t display all of the alerts and their clearing actions, so no matter how many times you run through the wizard, you’ll still get these alerts… unless you do the following:

1) Clear all alerts

2) Reinstate critical alerting to your “Critical” distribution list

3) Manually disable (via hex code) the alerts that aren’t shown in the web UI

Step 1: Clear all alerts

This walkthrough assumes you already have the latest firmware loaded on your APC NMC.  If this looks nothing like your UPS (e.g. your tabs are along the left-hand side), you’re not running the latest firmware.  Upgrade your firmware first by going to http://www.apc.com, clicking on “Software & Firmware,” locating & downloading the appropriate firmware specific to the model number of your Network Management Card, and following the directions in the ReadMe to get the firmware up-to-date.  In my experience, if you’re going from a way-outdated firmware version to the current version, you may have to try a couple of times, but it will work eventually (be patient).

1A) Go ahead and log into your APC NMC’s web UI, then go to Administration > Notification > Event Actions > by group:

     

1B) Choose “Events by Severity,” check all three boxes and hit Next:

      

1C) Choose “E-mail Recipients” and click Next:

      

1D) Check the box next to the e-mail address (you’ve already configured this under Administration > Notification > E-mail > recipients, right?) and click Next:

     

1E) Confirm the information matches the screenshot below (in particular the “Disable Notifications” radio button) and click Next:
     

1F) Confirm the “will not be notified” phrasing and click Apply… this will take 5-10 seconds:

     

1G) Click Finish:
     

Step 2: Reinstate critical alerting to your “Critical” distribution list

2A) Back on the Administration > Notification > Event Actions > by group page (see Step 1A), choose “Events by Severity” and check only the box next to “All Critical Events” and click Next:
     

2B) Choose “E-mail Recipeints” and click Next:

     

2C) Check the box next to the e-mail address and click Next:

     

2D) Confirm the settings below, especially the “Enable Notifications” selection… and turn off the repeat option so you don’t generate a heap of Critical tickets, then click Next:

   

2E) Confirm the settings and click Apply:

   

2F) Click Finish:
     

Step 3: Manually disable (via hex code) the alerts that aren’t shown in the web UI

3A) Go to the  Administration > Notification > Event Actions > by event page:

     

3B) Choose a random event category… I’m going to choose Battery:

     

3C) Now choose a random event… I’m going to choose “UPS: The number of batteries increased”:
     

3D) Take a look at your browser’s address bar… notice the hex code at the end?  This is what we’ll be changing in the next step:
     

3E) Substitute the hex code for 0x0105 (for “UPS: Passed a self-test”) and hit Enter:
     

3F) Un-check the box for the e-mail recipient and click Apply:
     

3G) If there are any other superfluous events (mostly “clearing” events) that you don’t want sent to the “Critical” distribution list, you can repeat steps 3E and 3F for those alerts as well… see “APC_NMC_Events.txt” (attached)

Hooray for not unnecessarily waking people up!

; System: Coldstart.
E0001=ES,E[:::],T[:::::],P[:::]

; System: Warmstart.
E0002=ES,E[:::],T[:::::],P[:::]

; System: SNMP configuration change.
E0003=ES,E[-:::],T[:::::],P[:::]

; System: Detected an unauthorized user attempting to access the SNMP interface.
E0004=ES,E[-:::],T[:::::],P[:::]

; System: Detected an unauthorized user attempting to access the Control Console interface.
E0005=ES,E[-:::],T[:::::],P[:::]

; System: Detected an unauthorized user attempting to access the Web interface.
E0006=ES,E[-:::],T[:::::],P[:::]

; System: Detected an unauthorized user attempting to access the FTP interface.
E0045=ES,E[-:::],T[:::::],P[:::]

; System: Network service started.
E0007=E,E[:+:+:],T[:::::],P[:::]

; System: Password changed.
E0008=ES,E[-:::],T[:::::],P[:::]

; System: Restarting.
E0009=E,E[:+:+:],T[:::::],P[:::]

; System: FTP File transfer started.
E000C=E,E[:+:+:],T[:::::],P[:::]

; System: TFTP File transfer started.
E000D=E,E[:+:+:],T[:::::],P[:::]

; System: File transfer failed.
E000F=E,E[:+:+:],T[:::::],P[:::]

; System: Console user logged in.
E0014=E,E[:+:+:],T[:::::],P[:::]

; System: Web user logged in.
E0015=E,E[:+:+:],T[:::::],P[:::]

; System: FTP user logged in.
E0016=E,E[:+:+:],T[:::::],P[:::]

; System: Reset to Defaults.
E0018=E,E[:+:+:],T[:::::],P[:::]

; System: Initializing data in the file.
E0019=E,E[:::],T[:::::],P[:::]

; System: Email information.
E001A=E,E[:+:+:],T[:::::],P[:::]

; System: TCP/IP stack failure.
E001D=E,E[:+:+:],T[:::::],P[:::]

; System: Console user logged out.
E001E=E,E[:+:+:],T[:::::],P[:::]

; System: Web user logged out.
E001F=E,E[:+:+:],T[:::::],P[:::]

; System: FTP user logged out.
E0020=E,E[:+:+:],T[:::::],P[:::]

; System: Set Date or Time.
E0021=E,E[:::],T[:::::],P[:::]

; System: Trace information.
E0024=,E[:::],T[:::::],P[:::]

; System: Data Log cleared.
E0023=E,E[:+:+:],T[:::::],P[:::]

; System: Modem dial-out failed.
E0025=ES,E[-:::],T[:::::],P[:::]

; System: RMS CLI user logged in.
E0026=E,E[:+:+:],T[:::::],P[:::]

; System: RMS CLI user logged out.
E0027=E,E[:+:+:],T[:::::],P[:::]

; System: Network service information.
E002A=E,E[:::],T[:::::],P[:::]

; System: Network service could not start.
E002B=E,E[:+:+:],T[:::::],P[:::]

; System: Network service stopped.
E002C=E,E[:::],T[:::::],P[:::]

; System: SSL Error: Invalid certificate.
E002D=E,E[:+:+:],T[:::::],P[:::]

; System: New certificate loaded.
E002E=E,E[:+:+:],T[:::::],P[:::]

; System: SSL enabled (now using HTTPS).
E002F=E,E[:+:+:],T[:::::],P[:::]

; System: SSL disabled (now using HTTP).
E0030=E,E[:+:+:],T[:::::],P[:::]

; System: Session Management enabled.
E0039=E,E[:::],T[:::::],P[:::]

; System: Session Management disabled.
E003A=E,E[:::],T[:::::],P[:::]

; System: WebServer could not start
E0031=E,E[:::],T[:::::],P[:::]

; System: DNS Network Error.
E0032=E,E[:+:+:],T[:::::],P[:::]

; System: Configuration change.
E0033=E,E[:+:+:],T[:::::],P[:::]

; System: Configuration file uploaded complete.
E0034=E,E[:+:+:],T[:::::],P[:::]

; System: Paging: Failed to send message.
E0035=E,E[:+:+:],T[:::::],P[:::]

; System: SSL information.
E0036=E,E[:+:+:],T[:::::],P[:::]

; System: SSH/SCP information.
E0037=E,E[:+:+:],T[:::::],P[:::]

; System: Certificate, host key, and log store information.
E0038=E,E[:::],T[:::::],P[:::]

; System: Set Daylight Saving Time.
E003D=E,E[:+:+:],T[:::::],P[:::]

; System: NTP update failure.
E003F=E,E[:+:+:],T[:::::],P[:::]

; System: Data Log Upload event.
E0040=E,E[:+:+:],T[:::::],P[:::]

; System: RMS failed to send email/modem.
E0041=E,E[:+:+:],T[:::::],P[:::]

; System: Event Log cleared.
E0013=E,E[:::],T[:::::],P[:::]

; System: Lost communications event manually cleared.
E0044=E,E[:+:+:],T[:::::],P[:::]

; UPS: Restored the local network management interface-to-UPS communication.
E0101=ES,E[:::],T[:::::],P[+:+:+:+]

; UPS: Lost the local network management interface-to-UPS communication.
E0102=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: The load exceeds 100% of rated capacity.
E0103=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: The load no longer exceeds 100% of rated capacity.
E0104=ES,E[:::],T[:::::],P[+:+:+:+]

; UPS: Passed a self-test.
E0105=ES,E[:::],T[:::::],P[:::]

; UPS: Failed a self-test.
E0106=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: The battery power is too low to support the load; if power fails, the UPS will be shut down immediately.
E0107=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: A discharged battery condition no longer exists.
E0108=ES,E[:::],T[:::::],P[:::]

; UPS: On battery power in response to an input power problem.
E0109=ES,E[--05S-30S00:::],T[:::::],P[:::]

; UPS: No longer on battery power.
E010A=ES,E[-:::],T[:::::],P[:::]

; UPS: The battery power is too low to continue to support the load; the UPS will shut down if input power does not return to normal soon.
E010F=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: A low battery condition no longer exists.
E0110=ES,E[:::],T[:::::],P[+:+:+:+]

; UPS: The output power is now turned on.
E0113=ES,E[:::],T[:::::],P[+:+:+:+]

; UPS: The output power is turned off.
E0114=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: Turned off for a defined period of time in response to a software command, or off while waiting for input power to return to normal.
E0115=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: Turned on after a defined period of time, or input power has returned to normal.
E0116=ES,E[:::],T[:::::],P[+:+:+:+]

; UPS: Started a reboot process.
E0117=ES,E[-:::],T[:::::],P[:::]

; UPS: At least one faulty battery exists.
E0119=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: A faulty battery no longer exists.
E011A=ES,E[:::],T[:::::],P[+:+:+:+]

; UPS: In bypass in response to the UPS front-panel or a user-initiated software command, typically for maintenance.
E011C=ES,E[--05S-30S00:::],T[:::::],P[:::]

; UPS: No longer in bypass.
E011E=ES,E[-:::],T[:::::],P[:::]

; UPS: Started a runtime calibration.
E0123=ES,E[-:::],T[:::::],P[:::]

; UPS: Completed a runtime calibration.
E0124=ES,E[-:::],T[:::::],P[:::]

; UPS: Graceful shutdown in progress.
E0125=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: A battery charger fault exists.
E012A=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: A battery charger fault no longer exists.
E012B=ES,E[:::],T[:::::],P[+:+:+:+]

; UPS: The internal battery temperature exceeds the critical threshold.
E012C=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: The internal battery temperature no longer exceeds the critical threshold.
E012D=ES,E[:::],T[:::::],P[+:+:+:+]

; UPS: Started a scheduled shutdown.
E0131=ES,E[-:::],T[:::::],P[:::]

; UPS: Failed a scheduled shutdown.
E0132=ES,E[-:::],T[:::::],P[:::]

; UPS: deleted a scheduled shutdown.
E0133=ES,E[-:::],T[:::::],P[:::]

; UPS: A synchronization command information message occurred.
E0136=ES,E[-:::],T[:::::],P[:::]

; UPS: Started a self-test.
E0137=E,E[-:::],T[:::::],P[:::]

; UPS: Lost the management interface-to-UPS communication while the UPS was on battery.
E0148=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: SNMP was used to issue a control command.
E0149=ES,E[-:::],T[:::::],P[:::]

; UPS: A power module fault exists.
E0201=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: A power module fault no longer exists.
E0202=ES,E[:::],T[:::::],P[+:+:+:+]

; UPS: A main intelligence module fault exists.
E0203=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: A main intelligence module fault no longer exists.
E0204=ES,E[:::],T[:::::],P[+:+:+:+]

; UPS: A redundant intelligence module fault exists.
E0205=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: A redundant intelligence module fault no longer exists.
E0206=ES,E[:::],T[:::::],P[+:+:+:+]

; UPS: A battery fault exists.
E0207=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: A battery fault no longer exists.
E0208=ES,E[:::],T[:::::],P[+:+:+:+]

; UPS: A load (kVA) alarm threshold violation exists.
E0209=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: A load (kVA) alarm threshold violation no longer exists.
E020A=ES,E[:::],T[:::::],P[+:+:+:+]

; UPS: Redundancy lost.
E020B=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: Redundancy returned.
E020C=ES,E[:::],T[:::::],P[+:+:+:+]

; UPS: A redundancy alarm threshold violation exists.
E020D=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: A redundancy alarm threshold violation no longer exists.
E020E=ES,E[:::],T[:::::],P[+:+:+:+]

; UPS: An input voltage or frequency problem prevents switching to bypass mode.
E020F=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: An input voltage or frequency problem no longer prevents switching to bypass mode.
E0210=ES,E[:::],T[:::::],P[+:+:+:+]

; UPS: The bypass relay is stuck in its bypass position.
E0211=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: The bypass relay is no longer stuck in its bypass position.
E0212=ES,E[:::],T[:::::],P[+:+:+:+]

; UPS: The bypass relay is stuck in its online position.
E0213=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: The bypass relay is no longer stuck in its online position.
E0214=ES,E[:::],T[:::::],P[+:+:+:+]

; UPS: In bypass in response to an internal hardware fault.
E0215=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: No longer in bypass.
E0216=ES,E[:::],T[:::::],P[+:+:+:+]

; UPS: In bypass in response to an overload.
E0217=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: No longer in bypass.
E0218=ES,E[:::],T[:::::],P[+:+:+:+]

; UPS: In bypass for maintenance.
E0219=ES,E[--05S-30S00:::],T[:::::],P[:::]

; UPS: No longer in bypass.
E021A=ES,E[-:::],T[:::::],P[+:+:+:+]

; UPS: The input circuit breaker is open.
E021B=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: The input circuit breaker is no longer open.
E021C=ES,E[:::],T[:::::],P[+:+:+:+]

; UPS: System level fan fault exists.
E021D=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: System level fan fault no longer exists.
E021E=ES,E[:::],T[:::::],P[+:+:+:+]

; UPS: The redundant intelligence module is in control.
E021F=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: The main intelligence module is now in control.
E0220=ES,E[:::],T[:::::],P[+:+:+:+]

; UPS: An internal communication bus fault exists.
E0221=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: An internal communication bus fault no longer exists.
E0222=ES,E[:::],T[:::::],P[+:+:+:+]

; UPS: No power modules detected as installed.
E0223=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: Power modules are now detected.
E0224=ES,E[:::],T[:::::],P[+:+:+:+]

; UPS: An input voltage or frequency problem occurred while in bypass, turning off the UPS.
E0225=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: The power problem that caused the UPS to turn off while in bypass no longer exists.
E0226=ES,E[:::],T[:::::],P[+:+:+:+]

; UPS: A runtime alarm threshold violation exists.
E0227=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: A runtime alarm threshold violation no longer exists.
E0228=ES,E[:::],T[:::::],P[+:+:+:+]

; UPS: An extended run frame fault exists.
E0229=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: An extended run frame fault no longer exists.
E022A=ES,E[:::],T[:::::],P[+:+:+:+]

; UPS: The output voltage is outside its defined limits.
E022B=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: The output voltage is no longer outside its defined limits.
E022C=ES,E[:::],T[:::::],P[+:+:+:+]

; UPS: A phase synchronization fault exists.
E022D=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: A phase synchronization fault no longer exists.
E022E=ES,E[:::],T[:::::],P[+:+:+:+]

; UPS: The battery is not installed properly.
E022F=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: The battery is now installed.
E0230=ES,E[:::],T[:::::],P[+:+:+:+]

; UPS: The battery voltage exceeds the nominal battery voltage rating.
E0231=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: The battery voltage no longer exceeds the nominal battery voltage rating.
E0232=ES,E[:::],T[:::::],P[+:+:+:+]

; UPS: Non-specific fault; Access UPS keyboard for details.
E0233=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: Non-specific fault cleared.
E0234=ES,E[:::],T[:::::],P[+:+:+:+]

; UPS: A site wiring fault exists.
E0235=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: A site wiring fault no longer exists.
E0236=ES,E[:::],T[:::::],P[+:+:+:+]

; UPS: The number of batteries increased.
E0241=ES,E[-:::],T[:::::],P[:::]

; UPS: The number of batteries decreased.
E0242=ES,E[-:::],T[:::::],P[:::]

; UPS: Number of Power Modules increased.
E0243=ES,E[-:::],T[:::::],P[:::]

; UPS: Number of Power Modules decreased.
E0244=ES,E[-:::],T[:::::],P[:::]

; UPS: The main intelligence module was inserted.
E0245=ES,E[-:::],T[:::::],P[:::]

; UPS: The main intelligence module was removed.
E0246=ES,E[-:::],T[:::::],P[:::]

; UPS: The redundant intelligence module was inserted.
E0247=ES,E[-:::],T[:::::],P[:::]

; UPS: The redundant intelligence module was removed.
E0248=ES,E[-:::],T[:::::],P[:::]

; UPS: The number of extended run frames increased.
E0249=ES,E[-:::],T[:::::],P[:::]

; UPS: The number of extended run frames decreased.
E024A=ES,E[-:::],T[:::::],P[:::]

; UPS: A system fault exists.
E0A01=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: A system fault no longer exists.
E0A02=ES,E[:::],T[:::::],P[+:+:+:+]

; UPS: A bypass relay failure exists.
E0A03=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: A bypass relay failure no longer exists.
E0A04=ES,E[:::],T[:::::],P[+:+:+:+]

; UPS: A power module turn off failure exists.
E0A05=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: A power module turn off failure no longer exists.
E0A06=ES,E[:::],T[:::::],P[+:+:+:+]

; UPS: A frame identification failure exists.
E0A07=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; UPS: A frame identification failure no longer exists.
E0A08=ES,E[:::],T[:::::],P[+:+:+:+]

; Environment: A critical fault exists for external Environmental Monitor input contact 1 ({name} at {location}).
E0301=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; Environment: A fault no longer exists for external Environmental Monitor input contact 1 ({name} at {location}).
E0302=ES,E[:::],T[:::::],P[+:+:+:+]

; Environment: A critical fault exists for external Environmental Monitor input contact 2 ({name} at {location}).
E0303=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; Environment: A fault no longer exists for external Environmental Monitor input contact 2 ({name} at {location}).
E0304=ES,E[:::],T[:::::],P[+:+:+:+]

; Environment: A critical fault exists for external Environmental Monitor input contact 3 ({name} at {location}).
E0305=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; Environment: A fault no longer exists for external Environmental Monitor input contact 3 ({name} at {location}).
E0306=ES,E[:::],T[:::::],P[+:+:+:+]

; Environment: A critical fault exists for external Environmental Monitor input contact 4 ({name} at {location}).
E0307=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; Environment: A fault no longer exists for external Environmental Monitor input contact 4 ({name} at {location}).
E0308=ES,E[:::],T[:::::],P[+:+:+:+]

; Environment: A minimum temperature threshold violation exists for external Environmental Monitor sensor 1 ({name} at {location}) reporting under {threshold}.
E0331=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; Environment: A minimum temperature threshold violation no longer exists for external Environmental Monitor sensor 1 ({name} at {location}).
E0332=ES,E[:::],T[:::::],P[+:+:+:+]

; Environment: A low temperature threshold violation exists for external Environmental Monitor sensor 1 ({name} at {location}) reporting under {threshold}.
E0309=ES,E[--05S-30S00:::],T[:::::],P[:::]

; Environment: A low temperature threshold violation no longer exists for external Environmental Monitor sensor 1 ({name} at {location}).
E030A=ES,E[-:::],T[:::::],P[:::]

; Environment: A high temperature threshold violation exists for external Environmental Monitor sensor 1 ({name} at {location}) reporting over {threshold}.
E030B=ES,E[--05S-30S00:::],T[:::::],P[:::]

; Environment: A high temperature threshold violation no longer exists for external Environmental Monitor sensor 1 ({name} at {location}).
E030C=ES,E[-:::],T[:::::],P[:::]

; Environment: A maximum temperature threshold violation exists for external Environmental Monitor sensor 1 ({name} at {location}) reporting over {threshold}.
E032F=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; Environment: A maximum temperature threshold violation no longer exists for external Environmental Monitor sensor 1 ({name} at {location}).
E0330=ES,E[:::],T[:::::],P[+:+:+:+]

; Environment: A minimum humidity threshold violation exists for external Environmental Monitor sensor 1 ({name} at {location}) reporting under {threshold}.
E0335=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; Environment: A minimum humidity threshold violation no longer exists for external Environmental Monitor sensor 1 ({name} at {location}).
E0336=ES,E[:::],T[:::::],P[+:+:+:+]

; Environment: A low humidity threshold violation exists for external Environmental Monitor sensor 1 ({name} at {location}) reporting under {threshold}.
E030D=ES,E[--05S-30S00:::],T[:::::],P[:::]

; Environment: A low humidity threshold violation no longer exists for external Environmental Monitor sensor 1 ({name} at {location}).
E030E=ES,E[-:::],T[:::::],P[:::]

; Environment: A high humidity threshold violation exists for external Environmental Monitor sensor 1 ({name} at {location}) reporting over {threshold}.
E030F=ES,E[--05S-30S00:::],T[:::::],P[:::]

; Environment: A high humidity threshold violation no longer exists for external Environmental Monitor sensor 1 ({name} at {location}).
E0310=ES,E[-:::],T[:::::],P[:::]

; Environment: A maximum humidity threshold violation exists for external Environmental Monitor sensor 1 ({name} at {location}) reporting over {threshold}.
E0333=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; Environment: A maximum humidity threshold violation no longer exists for external Environmental Monitor sensor 1 ({name} at {location}).
E0334=ES,E[:::],T[:::::],P[+:+:+:+]

; Environment: A minimum temperature threshold violation exists for external Environmental Monitor sensor 2 ({name} at {location}) reporting under {threshold}.
E0339=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; Environment: A minimum temperature threshold violation no longer exists for external Environmental Monitor sensor 2 ({name} at {location}).
E033A=ES,E[:::],T[:::::],P[+:+:+:+]

; Environment: A low temperature threshold violation exists for external Environmental Monitor sensor 2 ({name} at {location}) reporting under {threshold}.
E0311=ES,E[--05S-30S00:::],T[:::::],P[:::]

; Environment: A low temperature threshold violation no longer exists for external Environmental Monitor sensor 2 ({name} at {location}).
E0312=ES,E[-:::],T[:::::],P[:::]

; Environment: A high temperature threshold violation exists for external Environmental Monitor sensor 2 ({name} at {location}) reporting over {threshold}.
E0313=ES,E[--05S-30S00:::],T[:::::],P[:::]

; Environment: A high temperature threshold violation no longer exists for external Environmental Monitor sensor 2 ({name} at {location}).
E0314=ES,E[-:::],T[:::::],P[:::]

; Environment: A maximum temperature threshold violation exists for external Environmental Monitor sensor 2 ({name} at {location}) reporting over {threshold}.
E0337=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; Environment: A maximum temperature threshold violation no longer exists for external Environmental Monitor sensor 2 ({name} at {location}).
E0338=ES,E[:::],T[:::::],P[+:+:+:+]

; Environment: A minimum humidity threshold violation exists for external Environmental Monitor sensor 2 ({name} at {location}) reporting under {threshold}.
E033D=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; Environment: A minimum humidity threshold violation no longer exists for external Environmental Monitor sensor 2 ({name} at {location}).
E033E=ES,E[:::],T[:::::],P[+:+:+:+]

; Environment: A low humidity threshold violation exists for external Environmental Monitor sensor 2 ({name} at {location}) reporting under {threshold}.
E0315=ES,E[--05S-30S00:::],T[:::::],P[:::]

; Environment: A low humidity threshold violation no longer exists for external Environmental Monitor sensor 2 ({name} at {location}).
E0316=ES,E[-:::],T[:::::],P[:::]

; Environment: A high humidity threshold violation exists for external Environmental Monitor sensor 2 ({name} at {location}) reporting over {threshold}.
E0317=ES,E[--05S-30S00:::],T[:::::],P[:::]

; Environment: A high humidity threshold violation no longer exists for external Environmental Monitor sensor 2 ({name} at {location}).
E0318=ES,E[-:::],T[:::::],P[:::]

; Environment: A maximum humidity threshold violation exists for external Environmental Monitor sensor 2 ({name} at {location}) reporting over {threshold}.
E033B=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; Environment: A maximum humidity threshold violation no longer exists for external Environmental Monitor sensor 2 ({name} at {location}).
E033C=ES,E[:::],T[:::::],P[+:+:+:+]

; Environment: Restored the local network management interface-to-external Environmental Monitoring Card communication.
E0319=ES,E[:::],T[:::::],P[+:+:+:+]

; Environment: Lost the local network management interface-to-external Environmental Monitoring Card communication.
E031A=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; Environment: A critical fault exists for integrated Environmental Monitor input contact {number} ({name} at {location}).
E031B=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; Environment: A fault no longer exists for integrated Environmental Monitor input contact {number} ({name} at {location}).
E031C=ES,E[:::],T[:::::],P[+:+:+:+]

; Environment: A minimum temperature threshold violation exists for integrated Environmental Monitor sensor ({name} at {location}) reporting under {threshold}.
E0329=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; Environment: A minimum temperature threshold violation no longer exists for integrated Environmental Monitor sensor ({name} at {location}).
E032A=ES,E[:::],T[:::::],P[+:+:+:+]

; Environment: A low temperature threshold violation exists for integrated Environmental Monitor sensor ({name} at {location}) reporting under {threshold}.
E031D=ES,E[--05S-30S00:::],T[:::::],P[:::]

; Environment: A low temperature threshold violation no longer exists for integrated Environmental Monitor sensor ({name} at {location}).
E031E=ES,E[-:::],T[:::::],P[:::]

; Environment: A high temperature threshold violation exists for integrated Environmental Monitor sensor ({name} at {location}) reporting over {threshold}.
E031F=ES,E[--05S-30S00:::],T[:::::],P[:::]

; Environment: A high temperature threshold violation no longer exists for integrated Environmental Monitor sensor ({name} at {location}).
E0320=ES,E[-:::],T[:::::],P[:::]

; Environment: A maximum temperature threshold violation exists for integrated Environmental Monitor sensor ({name} at {location}) reporting over {threshold}.
E0327=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; Environment: A maximum temperature threshold violation no longer exists for integrated Environmental Monitor sensor ({name} at {location}).
E0328=ES,E[:::],T[:::::],P[+:+:+:+]

; Environment: A minimum humidity threshold violation exists for integrated Environmental Monitor sensor ({name} at {location}) reporting under {threshold}.
E032D=ES,E[+-05S-30S00:::],T[:::::],P[:::]

; Environment: A minimum humidity threshold violation no longer exists for integrated Environmental Monitor sensor ({name} at {location}).
E032E=ES,E[:::],T[:::::],P[+:+
views
10 responses
thanks a lot, we have a dp310 usv which sends mails over mails with the "non-specific fault" message and i didn't found a way to disable it. hopefully its over now :o)
tks, it wil help a lot.
Thanks mate. Thanks was a huge help
Thank you so much!!!! I was getting woke up by self test alerts!!!!
Great write-up. Thanks much for the undoc'd info.
Bless you for this info!
4 visitors upvoted this post.